Adjustment Type
- Factory Set (Pre-Set) One Switch
- Set Point Adjustment
Ambient Temperature Range
- -18° to 71° C (0° to 160° F) with Buna-N Construction
- -18° to 82° C (0° to 180° F) with Viton Construction
Applications
- Balers & Lube Oil Systems
- Compactors
- Industrial Applications
- Mobile Hydraulics Units
- OEM Applications
Approvals & Certifications
- ATEX Directive (94/9/EC) II 1 G EEx ia IIC T6 Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CRN
- CSA C22.2 No. 14, File # E42272
- GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 73/23/E & 93/68/EEC
- PED: 97/23/EC
- UL (C,US) 508
Approvals & Certifications
Deadband
- psi: 1 to 60 (kPa: 6.895 to 413.7, bar: 0.068 to 4.1)
Electrical Connectors
- 0.25” Push-On Terminals
- Common
Electrical Contacts
- Gold Flashing over Silver Contact for Loads down to 5 mA at 6 Vdc, 2 mA at 12 Vdc & 1 mA at 24 Vdc
- Normally Closed
- Normally Open
Electrical Rating
- 0.5 A Resistive, 0.25 A Inductive at 125 Vdc
- 5 A at 250 Vac
- 5 A Resistive, 3 A Inductive at 30 Vdc
- 5 A Resistive, 5 A Inductive (75 % Power Factor), at 125/250 Vac, 1/4 hp
Mounting
- 1/8” NPT Male
- Bracket Kit
- Surface
Name Plate, Tag Material
- Stainless Steel ID, Paper Tag & Wire Attachment
Overpressure & Static Pressure Limits
- Overpressure - psi: 1,000 to 2,500 (kPa: 6,895 to 17,240, bar: 68.9 to 172.4)
Process Connection Material
Proof Pressure
- psi: 3,000 (kPa: 20,685, bar: 206.8)
Repeatability
- Set Point Repeatability: ± 1 % of Full Scale Range
Service
- Oxygen Service Cleaning, Alcohol Cleaning to Remove Residue from the Process Connection
Set Point - Decreasing
- bar: 0.3 to 41.4
- kPa: 27.58 to 4,137
- psi: 4 to 600
Set Point - Increasing
- bar: 0.3 to 41.4
- kPa: 27.58 to 4,137
- psi: 4 to 600
Shock
- Set Point Repeats after 50 G, 10 millisecond Duration
Storage Temperature
- -40° to 82° C (-40° to 180° F)
System Pressure
- bar: 172.4
- kPa: 17,236
- psi: 2,500
Vibration
- Set Point Repeats after 10 G, 5 to 500 CPS