Ambient Temperature Range
- -10° to 55° C (15° to 130° F)
Cover Material
- Actuator: Nylon
- Actuator: Polyamide (PA 6.6)
Duty Cycle
- Rating: S4=50 % According to IEC 34
Electrical Connectors
- Cable Glands ISO M20
- Cable Plug According to EN 175301-803 (Supply Voltage)
Electrical Rating
- Limit Switches: 250 Vac / 1.5 A, Max.
Enclosure, Body Material
- Actuator: Nylon
- Polyamide (PA 6.6)
- Polypropylene (PP)
- PVC-C
- PVC-U
- PVDF
Environmental Protection
- IP66 with Cable Plug Installed
Flow Rate
- 4.8 to 204 m³/hour (Kv) - Water
Input
- Positioner Card with Normal: 0-10 V
- Positioner Card with Normal: 4-20 mA
Materials of Construction
- Actuator (Gear Box, Axis): Stainless Steel
- Actuator (Gearbox): Polycarbonate (PC)
Mounting
- Don't Mount the Actuator Upside Down
Operating Pressure
- PP-H - psi: 145 (kPa: 1,000, bar: 10)
- PVC-U, PVDF, PVC-C - psi: 232 (kPa: 1,600, bar: 16)
Operating Voltages
- 100-240 Vac at 50/60 Hz
- 100-350 Vdc
- 12-48 Vdc
- 15-30 Vac at 50/60 Hz
Orifice Size
- 0.39” to 1.96” (10 to 50 mm)
Pipe Connection
- 1” Pipe (DN 25)
- 1/2” Pipe (DN 15)
- 1-1/2” Pipe (DN 40)
- 1-1/4” Pipe (DN 32)
- 2” Pipe (DN 50)
- 2-1/2” Pipe (DN 65)
- 3/4” Pipe (DN 20)
Pressure Range
- PP - psi: 145 (kPa: 1,000, bar: 10)
- PVC-U, PVDF - psi: 232 (kPa: 1,600, bar: 16)
Process Temperature
- PP: 10° to 80° C (50° to 176° F)
- PVC-U: 0° to 60° C (32° to 140° F)
- PVDF: 0° to 120° C (32° to 248° F)
Resistance
- Input Resistance for Control (0-10 V): 10 kiloohms
- Input Resistance for Control (0-20 / 4-20 mA): 100 ohms
Response Time
- Rotation Time for 90°: 12 seconds
Seat / Seal Material
- Seal: EPDM
- Seal: FKM
- Seal: PTFE
Tolerance
- Voltage: ± 10 % - for 12-48 Vdc the Operating Voltage Should Not Go Below 11.5 V
Torque
- Actuator: 20 Nm (177 In/Lbs)