8039 Paddle Wheel Flowmeter with Optical Principle

Brand: Burkert Fluid Control Systems

This flowmeter with an extra-large display is specially designed to switch a valve and to establish a monitoring system or an On/Off control loop. Switching points can be programmed with the 3-key keypad under the display and the connection to the process in the piping is done with standard fittings. 

The version with a frequency output makes it possible to transmit the paddle wheel rotation speed (2 pulses/paddle wheel rotation) directly to a PLC.
Features
  • Indication, monitoring, transmitting and On/Off control in one device
  • Configurable outputs (Transistor or relay)
  • Optical measurement principle:
    • Insensitive to magnetic fields
    • Flow sense detection
    • Insensitive to ferromagnetic particles in the fluid

Specifications

Ambient Temperature Range

  • Operating & Storage: 0° to 60° C (32° to 140° F)

Approvals & Certifications

  • EMC: EN 50081-1, 50082-2
  • LVD EN 61010-1
  • PED 97/23/CE

Bearing Material

  • Ceramics (Al₂O3)

BSP Connection

  • G 1” Female
  • G 1/2” Female
  • G 1/2” Male
  • G 1/4” Male
  • G 1-1/2” Female
  • G 1-1/4” Female
  • G 2” Female
  • G 3/4” Female

Cable Length

  • 328.1 feet (100 metres)

Circuit Protection

  • Protect Against Short Circuit

Consumption

  • Current: ≤ 80 mA (without Load)

Cover Material

  • 20 % Glass Fibre Reinforced

Diameter

  • Pipe: 1/4 to 2” (DN06 to DN 50)

Display

  • Large Digital Display with 8-Characters

Electrical Connectors

  • 0.14 to 0.5 mm² Cross Section
  • Cable Plug: EN 175301-803
  • Free Positionable Male Fixed Connector M12-5-Pin for Female 5-Pin M12 Cable Plug

Enclosure, Body Material

  • Polycarbonate (PC)

Environmental Protection

  • IP65

Humidity

  • ≤ 80 % Relative Humidity, Non-Condensing

Indication

  • LED

Linearity

  • ± 0.5 % of Full Scale

Materials of Construction

  • Front Panel Folio: Polyester

Measuring Error

  • Standard K-factor: ± 3 % of Reading
  • Teach-In: ± 1 % of Reading

Measuring Range

  • 0.3 to 10 m/sec

NPT Connection

  • 1” NPT Female
  • 1/2” NPT Female
  • 1/2” NPT Male
  • 1-1/2” NPT Female
  • 1-1/4” NPT Female
  • 2” NPT Female
  • 3/4” NPT Female

Operating Voltages

  • 12-30 Vdc, Filtered & Regulated

Output

  • Transistor for Threshold, Frequency: 5-30 Vdc
  • Transistor for Threshold, Frequency: 700 mA - Max.

Output Format

  • Open Collector

Plug Material

  • Cable Plug: Polyamide (PA)

Pressure Range

  • bar: 0 to 10
  • kPa: 0 to 1,000
  • psi: 0 to 145.1

Process Temperature

  • -15° to 100° C (5° to 212° F)

Relay Output

  • 3 A at 250 Vac / 30 Vdc

Repeatability

  • ± 0.4 % of Reading

Reverse Polarity Protection

  • Yes

Seat / Seal Material

  • Seal: FKM

Shock

  • EN 60068-2-27

Supply Voltage

  • 12-30 Vdc

Switch Type

  • Threshold (NPN and/or PNP), Frequency (NPN): Transistor

Vibration

  • EN 60068-2-6

Viscosity

  • 300 cSt, Max.

Wetted Materials

  • Axis: Ceramics (Al₂O3)
  • Fitting: Brass
  • Holder, Paddle Wheel: PVDF
show more