Adjustment Type
- Captive Clamp Screws
- Factory Set (Pre-Set)
- Set Point Adjustment
Ambient Temperature Range
- -40° to 71° C (-40° to 160° F), Set Point Typically Shifts less than 1 % of Range for a 28° C (50° F) Ambient Temperature Change
Applications
- Energy Generation Including Pumps
- Industrial Gas Production
- Pulp & Paper
- Turbines & Compressors
- Water & Wastewater Treatment
Approvals & Certifications
- ATEX Ex directive (94/9/EC) II 1 G Ex ia IIC T6 Ga Tamb: -50° to 60° C (-58° to 140° F)
- CE
- CSA C22.2 No. 14, File # E42272
- FM Class 3545
- GOST-R 51330.0, 51330.1, 51330.10 & 51330.14
- Low Voltage Directive (LVD) 2006/95/EC
- PED: 97/23/EC
- UL (C,US) 508
Approvals & Certifications
Deadband
- psi: 60 to 800 (kPa: 420 to 5,520, bar: 4.2 to 55.2)
Electrical Connectors
- 7/8” Hole to 1/2” NPT Female Watertight Conduit Fitting
- One 3/4” NPT
- Screw Terminal
- Two 7/8” Diameter Knockouts
Electrical Contacts
- Gold Contacts, 1 A at 125 Vac Resistive
- Normally Closed
- Normally Open
Electrical Rating
- 1 A at 125 Vac Resistive
- 10 A at 125 Vdc Resistive, Deadband & Min. Set Point Will Increase
- 20 A, 125/250/480 Vac Resistive
- Close Deadband, 5 A at 125/250 Vac Resistive
- External Manual Reset, High Ambient, 15 A at 125/250/480 Vac Resistive, Temperatures up to 145° C (250° F)
- Vapor Sealed, Fungus Resistant Case,15 A 125/250 Vac Resistive
Enclosure, Body Material
- Gasketed Die Cast Aluminum
Environmental Protection
- Intrinsically Safe
- IP66
- NEMA 4X
- Weathertight
Indication
- Single Red Status Light, 115 Vac
Name Plate, Tag Material
- Stainless Steel, Paper ID Tag & Wire Attachment
Overpressure & Static Pressure Limits
- Over Range Pressure - psi: 6,000 (kPa: 41,369, bar: 413.7)
Process Connection Material
Proof Pressure
- psi: 10,000 (kPa: 68,948, bar: 689.5)
Repeatability
- Set Point Repeatability: ± 3 % of Full Scale Range
Service
- Oxygen Service Cleaning, Alcohol Cleaning to Remove Residue from the Process Connection
Set Point - Decreasing
- bar: 6.9 to 413.7
- kPa: 689.5 to 41,369
- psi: 100 to 6,000
Set Point - Increasing
- bar: 6.9 to 413.7
- kPa: 689.5 to 41,369
- psi: 100 to 6,000
Shock
- Set Point Repeats after 15 G, 10 millisecond Duration
Storage Temperature
- -54° to 71° C (-65° to 160° F)
Switch Type
- DPDT Switch, 10 A at 125/250 Vac Resistive, Deadband & Min. Set Point Will Increase
- Two SPDT Switch, may be separated up to 100 % of Range
Vibration
- Set Point Repeats after 2.5 G, 5 to 500 Hz