Adjustment Type
- Factory Set (Pre-Set)
- Field Adjustable
Ambient Temperature Range
- -1° to 71° C (30° to 160° F)
Approvals & Certifications
Electrical Rating
- 5 A at 125 Vac & 250 Vac, 1/4 hp 5 A & 3 A at 30 Vdc & 0.5 A & 0.25 at 125 Vdc
- 5 mA at 6 Vdc, 2 mA at 12 Vdc, 1 mA at 24 Vdc
Mounting
- By Pressure Connections
- Surface
Set Point - Decreasing
- bar: 0.068 to 3.1
- kPa: 6.894 to 310.2
- psi: 1 to 45
Set Point - Increasing
- bar: 0.068 to 3.1
- kPa: 6.894 to 310.2
- psi: 1 to 45
System Pressure
- bar: 10.3
- kPa: 1,034